Thursday, July 29, 2010

tomco fire systems

hydrovisionshow2010b copy

Low Pressure CO2 Systems

Download the TOMCO2 Fire Systems Engineering Manual

Low Pressure Engineering Manual :: PDF File TOMCO2 Low Pressure Engineering Manual

 

Warning Signs

Warning signs are for installation in and around a protected space to alert personnel in case of an alarm. Signs are furnished with 4 holes and an adhesive backing or ease of installation.

> Read More on Warning Signs

 

Storage Tanks

The low pressure storage tank consists of a pressure vessel, insulation, refrigeration unit, instrumentation, fill connections, instrumentation connections and a flanged outlet to withdraw carbon dioxide at a high rate of flow. Storage tanks are available in sizes ranging from 3/4 ton thru 60 ton.

> Read more on Storage Tanks

 

1/2" - 2" Radial Nozzle

The Radial Nozzle is for use strictly on total flood systems. The nozzles are factory drilled in 1/2 code increments. Maximum listed coverage area is 36’ x 36’ [11m x 11m].

> Read more on 1/2" - 2" Radial Nozzles

 

1/2” 100psi Pressure Regulator

The pressure regulator is a fully automatic pressure regulating valve. The regulator is installed in the actuation line to maintain the 100psi required to operate the master / selector valves. The regulator
should be installed as close as possible to the vapor source on the storage tank.

> Read more on 1/2” 100psi Pressure Regulator

   

Pressure Relief Valve

The pressure relief valves are used to prevent damage to master / selector valves due over pressurization of the actuation line and to relieve pressure in a potentially trapped section of piping.

> Read more on Pressure Relief Valves

   

Pneumatic Time Delay Cabinet

The TOMCO2 Fire Systems pneumatic time delay cabinet is a pneumatically operated assembly of a pressure gauge, supervisory pressure switches, dial timers, 24vdc solenoid and mechanical override all interconnected by tubing and mounted in a NEMA 12, 4 or 4x enclosure. Three 1/2” [12.7] NPT connections on the enclosure provide connections for the necessary external piping.

> Read more on Pneumatic Time Delay Cabinets

   

Pneumatic Siren

The pneumatic siren is used in systems where audible warning is critical even in the event of a power failure. If siren is connected directly to discharge piping the connection shall be from the top of the pipe. If connected to a pneumatic time delay cabinet refer to the pneumatic time delay cabinet data sheet for connection details.

> Read more on Pneumatci Sirens

   

Page 1 of 3

A Winning Combination!TOMCO2 FOGEX® High Pressure Water Mist & Low Pressure CO2 Systems

Fire Systems News

Developments in CO2 technology have always been in the forefront. We are FM® approved on a complete line of low pressure CO2 equipment that is the only system that has been tested to the most recent addition of NFPA 12 (2005 Edition) and the FM® standard 5420 for CO2 systems. We look forward to a long, innovative and successful future, and we hope that you will consider TOMCO2 for your next CO2 fire system purchase.


Memberships:
National Fire Protection Association
Certifications:
FM Approved – Factory Mutual Approved for Carbon Dioxide Fire Extinguishing Systems

TOMCO2 Fire Systems

7619 Hamilton Avenue
Cincinnati, OH 45231
Phone: 513-729-FIRE
Fax: 513-729-3444